Motor Current Analysis

Proviso Systems Ltd are able to offer two choices in the motor current analysis field:-

1) We can supply an intelligent online solution. The Artesis MCM (Motor Current Monitor) which encompasses the following

  • Artesis MCM LV Line  (for Low Voltage Line-driven Motors)
  • Artesis MCM LV Inverter  (for Low Voltage Inverter-driven Motors)
  • Artesis MCM MV&HV  (for Medium & High Voltage Motors)
  • Artesis MCM MV&HV  (for Military applications)

 

2) We can carry out Motor Current Analysis as a field service. (Larger AC Motors Only)

 

 

Induction Motor Testing

"Motor Monitor"

Motor Current Analysis

 

Early Detection of rotor related faults in AC Induction Motors

  • Cracked or broken rotor bars
  • Cracked rotor end rings
  • High resistance joints in squirrel cage windings
  • Casting porosities or blow holes in aluminium
  • Poor joint brazing in fabricated rotors
  • Rotor winding problems in slip-ring induction motors
  • Stationary or rotating air gap irregularities
  • Unbalanced magnetic pull
  • Mechanical unbalance
  • Bent shaft, thermal bow
  • Out-of-round stator, rotor or bearings.

 

SUMMARY SHEET

 

Motor ID Fault Index Status
     
ACC Fan 01 UA 0.5 Pass
ACC Fan 01 UF 0.4 Pass
ACC Fan 01 XA 0.5 Pass
ACC Fan 01 WB 0.6 Caution
ACC Fan 01 VA 0.6 Caution
ACC Fan 01 YD 0.7 Caution
Fin Fan 2/10 0.2 Pass
Fin Fan 2/12 0.3 Pass

EXAMPLE OF MOTOR WITH DAMAGED ROTOR

Motor tag no No19 Power 100HP
Site   Volts

415

Train   Full load amps

125

Duty Motor Efficiency

93%

Serial no B500E Power factor

0.89

Frame size CW 250S No load amps

32.5

Manufacturer Brook Crompton Rotor bars  
Rated RPM

1,465

Starts per day

72

Line freq, Hz

50

Rotor type

4

Poles

4

Calibration

1

 

---------Rotor Damage Level-----

Date Time Moderate Severe

DDMMYY HHMM Amps % Indx 0 1 2 3 4 5 6

------ ---- ---- --- ---- I---+---+---+---+---+---+->

020497 1735 59.3 28 7.5 **************************>

Rotor winding condition recommendation No.19 03/04/97

This rotor winding has developed several broken bars. The risk of

secondary damage to the stator winding, or other elements of the motor, could be imminent. It is recommended that this motor be removed from service immediately.

 

 

 

 

 

 

 

 

 

ACC FAN 01 UA

Motor tag no ACC01UA Power KW

75

Site Example Volts

415

Train Air Cooled Condenser Full load amps

150

Duty Fan Efficiency

78%

Serial no CNM-CNDM-01-UA Power factor

0.89

Frame size 315SN-D No load amps

52.5

Manufacturer Brook Hansen Rotor bars  
Rated RPM

740

Starts per day  
Line freq Hz

50

Rotor type

4

Poles

8

Calibration

1

 

---------Rotor Damage Level----- ------Air Gap---------

Date Time Moderate Severe Dynamic Static

DDMMYY HHMM Amps % Indx 0 1 2 3 4 5 6 0 20 40 60 Change

------ ---- ---- --- ---- I---+---+---+---+---+---+->

28/07/99 1429 140. 89 .5 **

Rotor winding condition recommendation ACC-01-UA 28/07/99

This rotor winding is in a healthy condition and should be re-surveyed

in twelve months from this date or after 200 starts, whichever is first.

Extended Analysis:

You are advised to enter BUILD details to test for mechanical influences.

Latest date for next Rotor Survey - 28th July 2000.

 

 

 

 

 

 

 

 

 